Certificates and test reports

Our facade elements are made of reinforced polystyrene with a 3–5 mm protective acrylic layer, Merolith D10f. This layer is what faces rain, frost and sun, so we had it tested by independent accredited laboratories in Ukraine.

Below are the three test reports: adhesion to the substrate, fire behavior and frost resistance. Each document opens as a PDF (English translation of the original).

Adhesion to the substrate — Merolith D10f, Technical report No. 1 dated 02/08/2013 (tested 01/08/2013)

Adhesion to the substrate

0.87 MPaaverage adhesion strength, 15 tests

Document
Technical report No. 1 dated 02/08/2013 (tested 01/08/2013)
Laboratory
Tekhnotest Engineering, Kyiv (attested laboratory, certificate No. ПТ-138/12)
Method
Pull-off test, Ukrainian standard DSTU B V.2.6-36-2008, on asbestos-cement board
Results
0.95 MPa average at 20 °C, 0.84 MPa after heating to +80 °C, 0.82 MPa after freezing to −20 °C; adhesive failure in every test
Open PDF (5 pages)
Fire behavior — Merolith D10f, Test protocol No. 83/2Ц/1-2013 dated 30/07/2013 (tested 22/07/2013)

Fire behavior

Group F1low-flammability material

Document
Test protocol No. 83/2Ц/1-2013 dated 30/07/2013 (tested 22/07/2013)
Laboratory
Scientific and Research Center “Fire Safety” of the Ukrainian Civil Protection Research Institute (accreditation No. 2H278)
Method
Ukrainian standard DSTU B V.2.7-19-95 (GOST 30244-94), 12 samples 2.8 mm thick on asbestos-cement board
Results
smoke fumes 100 °C (F1 limit 135 °C), damaged length 26% (limit 65%), mass loss 1% (limit 20%), no self-burning and no burning drops
Open PDF (5 pages)
Frost resistance — Merolith D10f, Protocol No. 53-13/20 dated 11/09/2013 (tested 06/08–11/09/2013)

Frost resistance

100 cyclesof freezing and thawing with no delamination or damage

Document
Protocol No. 53-13/20 dated 11/09/2013 (tested 06/08–11/09/2013)
Laboratory
Test Center of building materials of the Ukrainian Research and Design Institute for building materials and products (accreditation No. 2T204)
Method
Ukrainian standards DSTU B V.2.7-233:2010, DSTU B V.2.7-126:2011 and DSTU B V.2.7-48-96 (GOST 10060.1-95)
Results
the samples withstood 100 cycles with no delamination or other damage (the standard requires at least 50)
Open PDF (2 pages)

Good to know

  • The tests were carried out in 2013 for GrafGroup (Graf Group LLC, Kyiv), the manufacturer of our facade elements.
  • Classes follow the Ukrainian DSTU standards named in each report; they are not Euroclasses (EN 13501-1).
  • As the laboratories state, each report applies only to the samples tested.

See also our catalog and our completed projects.